Valve Sizing

Valve sizing on a control valve is very important. The sizing graphs below are designed to assist in the selection of the correct valve size. When sizing a control valve the valve will control at a optimum between 20% and 80% capacity where 20% is the minimum flow and the 80% the maximum flow rate. This will prevent the valve from operating too close to the seat or from losing control during high flow.

Pressure Drop Chart

angle pressure drop chart
Valve Size50 mm80 mm100mm150 mm200 mm250 mm300 mm350 mm400 mm
Minimum Flow4.5 m³/h6 m³/h211.5 m³/h19 m³/h39 m³/h67 m³/h78 m³/h85 m³/h122 m³/h
Normal Flow44 m³/h69 m³/h129 m³/h310 m³/h508 m³/h905 m³/h1290 m³/h1501 m³/h1879 m³/h
Maximum Flow60 m³/h108 m³/h168 m³/h414 m³/h710 m³/h1120 m³/h1354 m³/h1940 m³/h2200 m³/h

Normal flow @ 6m/s
Maximum flow @ 7.6m/s

System Sizing

Another important factor to remember is that control valves can be installed in a parallel system (to increase flow range) or series system (to increase pressure range).
With a low flow condition, the option can be to install a V Port. The V Port allows for smooth operation close to the valve seat, at low flow conditions.

Series system

When the pressure reduction ratio through a control valve exceeds 5:1, it is recommended to have two valves in series installed. The pressure reduction will then be done in two stages.

Scroll to Top